Free tool
Max Zs calculator
Work out the maximum earth fault loop impedance for a protective device from Ia, then check a circuit from Ze and (R1 + R2), including readings taken cold.
How it works
Zs(max) = (U0 × Cmin) ÷ Ia
- U0 = 230 V, the nominal voltage to earth.
- Cmin = 0.95, the minimum voltage factor. IET Wiring Matters (issue 105, May 2025) gives it as 0.95 for a low voltage supply provided under the ESQCR.
- Ia comes from the device data.
The circuit figure is Zs = Ze + (R1 + R2). The maximum applies with the conductors at operating temperature, but test readings are taken cold, so the calculator checks a cold reading two ways, as in the Inspection and Testing Calculations workbook:
- Rule of thumb: Zs from room-temperature readings ≤ 0.8 × the maximum Zs. It is quick and cautious because it also scales Ze, which does not warm up with the circuit.
- Corrected to operating temperature: hot (R1 + R2) = (R1 + R2) × 1.20, then Zs = Ze + hot (R1 + R2), compared with the full maximum. The 1.20 multiplier takes (R1 + R2) from about 20 °C to 70 °C. The IET gives 70 °C as the assumed conductor operating temperature for the tabulated maximum Zs values (IET Inspection and Testing FAQs), and 70 °C is the rating of thermoplastic (PVC) insulation (IET Wiring Matters 93).
A reading that fails the rule of thumb is not automatically a failure: check it properly with the corrected method. A reading that is already above the full maximum while cold does not comply. The 0.8 factor and the 1.20 multiplier are the workbook’s practice values; which approach to use, and the factor, depend on the guidance you work to.
Rounding. Maximum figures are rounded down and circuit figures rounded up, to 4 decimal places, and the check uses the figures as shown, so rounding can never turn a fail into a pass.
See it worked by hand: How to calculate maximum Zs: worked examples.