When you test a circuit you need two figures: its earth fault loop impedance Zs, and the most its protective device will allow. This post shows how to work out that maximum and check a circuit against it. The three examples are taken word for word from our Inspection and Testing Calculations workbook, with the same working and rounding.
What maximum Zs means
Zs is the impedance of the whole fault loop: the supply, the line conductor out to the fault, and the protective conductor back. The higher it is, the lower the fault current. If the fault current is too low, the protective device will not operate within the required disconnection time, so every device has a maximum Zs.
The circuit figure is Zs = Ze + (R1 + R2). The maximum comes from the device.
The formula
Zs(max) = (U0 × Cmin) ÷ Ia
- U0 is the nominal voltage to earth. The examples use 230 V.
- Cmin is the minimum voltage factor, which allows for the supply voltage varying. IET Wiring Matters (issue 105, May 2025) gives it as 0.95 for a low voltage supply provided under the ESQCR.
- Ia is the current that makes the device operate within the required time. It comes from the device data.
With these figures the top line is always 230 × 0.95 = 218.5, so each maximum is 218.5 divided by Ia.
A note on the figures
These examples come from the workbook, so its copyright-page note applies to them too:
Practice data only. All figures in the questions, including maximum earth fault loop impedances, resistances per metre, cable ratings, voltage drop figures, correction factors, diversity allowances and time limits, are supplied for calculation practice. Conductor resistances, voltage-drop figures and some cable current ratings used in the questions are typical published values for copper cable, given so the questions can be worked. No figure in this book may be used for design, installation, inspection, testing or certification. Always check against your own copy of the current edition of BS 7671, the relevant IET guidance and the manufacturer’s data.
Example 1: the maximum Zs for a small device
Question (workbook Q54, Core): A small protective device operates within the required time when the fault current is at least 30 A (Ia, given).
- Use Zs(max) = (U0 × Cmin) ÷ Ia, with U0 = 230 V and Cmin = 0.95
Calculate the maximum Zs to 3 decimal places.
Method and numbers
- Zs(max) = (230 × 0.95) ÷ 30 = 7.283 Ω
Result
- Zs(max) = 7.283 Ω
One division gives the answer.
Example 2: does the circuit comply?
Question (workbook Q53, Core): A protective device operates within the required disconnection time when the fault current is at least 200 A (this is Ia, taken from the device data given).
- Use Zs(max) = (U0 × Cmin) ÷ Ia, with U0 = 230 V and Cmin = 0.95; this maximum applies with the conductors at operating temperature
- Circuit: Ze = 0.35 Ω, (R1 + R2) at 20 °C = 0.80 Ω
- Multiplier from 20 °C to operating temperature: 1.20
Calculate the maximum Zs to 4 decimal places, then the circuit Zs at operating temperature, and say whether the circuit complies.
Method and numbers
- Zs(max) = (230 × 0.95) ÷ 200 = 1.0925 Ω
- Hot (R1 + R2) = 0.80 × 1.20 = 0.960 Ω
- Zs = 0.35 + 0.960 = 1.31 Ω
- 1.31 Ω > 1.0925 Ω, so the circuit does not comply.
Result
- Zs(max) = 1.0925 Ω
- Zs at operating temperature = 1.31 Ω
- The circuit does not comply (1.31 Ω > 1.0925 Ω)
Maximum Zs figures apply with the conductors at operating temperature, but (R1 + R2) is measured cold, so the working multiplies it by 1.20 first. The hot Zs is over the maximum, so the circuit fails.
Example 3: changing the protective device
Question (workbook Q62, Challenging): An existing circuit has Zs = 1.21 Ω at conductor operating temperature (worked out from its test readings, given). Its protective device (with Ia = 160 A) is to be replaced with a different device whose Ia = 200 A.
- Use Zs(max) = (U0 × Cmin) ÷ Ia, U0 = 230 V, Cmin = 0.95; this maximum applies with the conductors at operating temperature
Calculate the maximum Zs for each device (4 d.p.) and say whether the circuit complies with each.
Method and numbers
- Zs(max) existing = 218.5 ÷ 160 = 1.3656 Ω
- Zs(max) replacement = 218.5 ÷ 200 = 1.0925 Ω
- 1.21 Ω ≤ 1.3656 Ω, so it complies with the existing device.
- 1.21 Ω > 1.0925 Ω, so it does not comply with the replacement device.
Result
- Existing device Zs(max) = 1.3656 Ω
- Replacement device Zs(max) = 1.0925 Ω
- It complies with the existing device (1.21 Ω ≤ 1.3656 Ω)
- It does not comply with the replacement device (1.21 Ω > 1.0925 Ω)
The Zs itself has not changed. The replacement device needs a larger current to operate in time, so its maximum Zs is lower and the same circuit no longer complies. Check Zs against the new device whenever a device is changed for one with a different Ia.
Common slips
- Leaving out Cmin and dividing 230 by Ia. That gives a maximum that is too high.
- Using Ia for a different device type or rating.
- Comparing a cold reading straight with the maximum. Correct (R1 + R2) to operating temperature first, or use the rule-of-thumb limit from the workbook’s temperature section.
- Rounding the maximum up, or the circuit figure down, so a circuit that is just over the limit appears to pass.